Cartridge operated water fire extinguishers Wi6CS | Wi9CS
The DÖKA CS-series with composite valve features an internal propellant cartridge and a strike-knob activation mechanism. The extinguisher is pressurized only when needed by pulling the safety pin and pressing the strike knob. This ensures high operational reliability, reduces wear on materials, and guarantees a long service life.
The extinguishing agent: Aqueous solution
The extinguishing effect relies on the heat-absorbing capacity (heat capacity) of water. The seat of the fire is rapidly cooled, thereby halting combustion. The extinguishing agent consists of water and an additive. It is completely free of PFOS and PFOA.
Outstanding extinguishing performance
Thanks to the addition of additives, the Wi6CS achieves a rating of 34A. The WiCS achieves a rating of 43A.
Fundamental protection for fire class A
With a rating of 34A, the Wi6CS is suitable for areas such as archives, libraries, warehouses, and workshops. It extinguishes solid, ember-forming materials such as wood, cardboard, paper, and textiles. Thanks to the simple composition of the extinguishing agent, collateral damage following its use remains minimal.
For those requiring a larger reserve of extinguishing agent, the Wi9CS with a rating of 43A is an available option.
Versions
Capacity: 6 ltr. Aqueous solution
Rating: 34A
Dimensions H x W x D ca. mm: 560 x 235 x 170
Weight ca. kg: 10,2
Throw range ca. m: 9-11
Discharge time ca. Sek.: 41
Operating temp. °C: 0 to +60
Packaging: Single packaging, 56 Units per palett
Capacity: 9 ltr. Aqueous solution
Rating: 43A
Dimensions H x W x D ca. mm: 620 x 270 x 195
Weight ca. kg: 14,8
Throw range ca. m: 9-11
Discharge time ca. Sek.: 76
Operating temp. °C: 0 to +60
Packaging: Single packaging, 30 Units per palett
Features
GPSR Information
Product data sheet: see Downloads
Operating instructions and declaration of conformity: see Downloads
Material safety data sheet for extinguishing agents: see Downloads
Safety instructions
- Operate the fire extinguisher in accordance with the pictograms and instructions printed on the fire extinguisher‘s operating plate, taking into account the additional information and instructions.
- The minimum and maximum temperature limits specified on the operating plate must be observed. Do not expose to cold or heat radiation if this causes the minimum or maximum temperature limit to be exceeded or fallen short of. Store fire extinguishers in frost-free areas. Protect from UV radiation.
- The use of CO2 and powder fire extinguishers can lead to electrostatic charging.
- CO2 fire extinguishers may only be used when people are present in rooms if there is a free floor area of >5.5 m² per kg of CO2. There is a risk of suffocation. • Do not direct the extinguishing agent jet at people from a short distance, especially not at the head. There is a risk of suffocation and CO2 fire extinguishers can cause cold burns.
- Fire extinguishers can be pressurised. Do not expose to force, do not open by force.
- If pressurised parts are damaged or corroded, the fire extinguisher must be depressurised and repaired immediately by a competent person.
- Only use fire extinguishers for their intended purpose. Do not make any structural modifications. • Fire extinguishers must be installed or set up in such a way that they are easily visible and accessible and protected against falling over or falling down and damage.
- Never carry fire extinguishers loose in the vehicle. Transport is only permitted with proper securing and in the original sealed carton or equivalent safety measures. Special brackets are required to carry fire extinguishers on or in vehicles at all times, and these must be fitted professionally. Fire extinguishers must be mounted in such a way that they cannot be damaged by the expected vibrations or movements, or even fall out of the holder. If the fire extinguisher is to be mounted on the outside of the vehicle, it must also be placed in a protective container.
- Keep fire extinguishers clean, do not use aggressive cleaning agents, only clean with a damp cloth.
- Only have fire extinguishers completely emptied and depressurised disposed of by a recognised disposal company.
- For cooking oil and cooking fat fires, only use fire extinguishers specially designed for fire class F!
- Keep away from children
Packaging consisting of*:
| Outer carton, cardboard, PAP 20 | ![]() |
| PE-LD protective film | ![]() |
* Details for standard shipping
- Fire extinguisher
- Wall bracket
- Operating Instructions / Declaration of Conformity
Technische Daten
| Operating system | Cartridge operated CS-Series |
|---|---|
| Fire class A Rating | 34 43 |
| Capacity | 6 ltr. 9 ltr. |
| Extinguishing agent | Aqueous solution |
| Temperature range °C | 0 to +60 |