Carbon dioxide fire extinguisher with steel cylinder

Reference 1505-6170
Choose type

Carbon dioxide fire extinguishers KS2CS-1 | KS5CS-1

The DÖKA CO₂ fire extinguishers KS2CS-1 and KS5CS-1 have an extinguishing agent cylinder made of steel. The high-quality polyester resin coating is tough and weatherproof and protects the extinguishing agent container from corrosion. The all-metal fitting consists of a base body made of nickel-plated brass and a lever set made of steel, which is powder-coated to protect against corrosion. For mounting on the wall, these fire extinguishers are equipped with a steel strap as standard.

The extinguishing agent: Carbon dioxide

Carbon dioxide (CO2) is a colorless and odorless gas. It is about 1.5 times heavier than air and is contained in the air we breathe. It is popularly called carbonic acid and it is used for many other applications. The extinguishing effect of carbon dioxide is based on the sticking effect.

Residue-free

After extinguishing, carbon dioxide leaves no extinguishing agent residues, it evaporates completely without leaving any residues.

Versions

Capacity: 2 kg carbon dioxide
Rating: 34B
Dimensions H x W x D ca. mm: 490 x 245 x 125
Weight ca. kg: 6,6
Throw range ca. m: 3
Discharge time ca. Sek.: 8
Operating temp. °C: -30 to +60
MED-Approval: No

Packaging: Single packaging, 64 Units per palett

Capacity: 5 kg carbon dioxide
Rating: 89B
Dimensions H x W x D ca. mm: 740 x 290 x 165
Weight ca. kg: 13,9
Throw range ca. m: 4
Discharge time ca. Sek.: 14
Operating temp. °C: -30 to +60
MED-Approval: Yes

Packaging: Single packaging, 30 Units per palett

Features

GPSR Information

DÖKA Feuerlöschgerätebau GmbH
Antonius-Raab-Straße 18
34123 Kassel
Deutschland

Kontakt

Product data sheet: see Downloads
Operating instructions and declaration of conformity: see Downloads
Material safety data sheet for extinguishing agents: see Downloads

Safety instructions

  • Operate the fire extinguisher in accordance with the pictograms and instructions printed on the fire extinguisher‘s operating plate, taking into account the additional information and instructions.
  • The minimum and maximum temperature limits specified on the operating plate must be observed. Do not expose to cold or heat radiation if this causes the minimum or maximum temperature limit to be exceeded or fallen short of. Store fire extinguishers in frost-free areas. Protect from UV radiation.
  • The use of CO2 and powder fire extinguishers can lead to electrostatic charging.
  • CO2 fire extinguishers may only be used when people are present in rooms if there is a free floor area of >5.5 m² per kg of CO2. There is a risk of suffocation. • Do not direct the extinguishing agent jet at people from a short distance, especially not at the head. There is a risk of suffocation and CO2 fire extinguishers can cause cold burns.
  • Fire extinguishers can be pressurised. Do not expose to force, do not open by force.
  • If pressurised parts are damaged or corroded, the fire extinguisher must be depressurised and repaired immediately by a competent person.
  • Only use fire extinguishers for their intended purpose. Do not make any structural modifications. • Fire extinguishers must be installed or set up in such a way that they are easily visible and accessible and protected against falling over or falling down and damage.
  • Never carry fire extinguishers loose in the vehicle. Transport is only permitted with proper securing and in the original sealed carton or equivalent safety measures. Special brackets are required to carry fire extinguishers on or in vehicles at all times, and these must be fitted professionally. Fire extinguishers must be mounted in such a way that they cannot be damaged by the expected vibrations or movements, or even fall out of the holder. If the fire extinguisher is to be mounted on the outside of the vehicle, it must also be placed in a protective container.
  • Keep fire extinguishers clean, do not use aggressive cleaning agents, only clean with a damp cloth.
  • Only have fire extinguishers completely emptied and depressurised disposed of by a recognised disposal company.
  • For cooking oil and cooking fat fires, only use fire extinguishers specially designed for fire class F!
  • Keep away from children

Packaging consisting of*:

Outer carton, cardboard, PAP 20
PE-LD protective film

* Details for standard shipping

  • Fire extinguisher
  • Wall bracket
  • Operating Instructions / Declaration of Conformity
Reference 1505-6170 Category CO2-Fire extinguishers

Technische Daten

Operating system Permanent pressure
Fire class B Rating 34 89
Capacity 2 kg 5 kg
MED Approval Yes (see product description)
Temperature range °C -30 to +60
Safety valve Yes

Question about this product

 
Loading...
Back to top