Cartridge operated powder fire extinguishers CS-Series

Reference 1414-0100
Choose type

Cartridge operated ABC dry powder fire extinguishers
Gi6CS-03 | Gi6CS-04 | Gi9CS | Gi12CS

The CS-Series with composite valve

The DÖKA CS-series with composite valve features an internal propellant cartridge and a strike-knob activation mechanism. The extinguisher is pressurized only when needed by pulling the safety pin and pressing the strike knob. This ensures high operational reliability, reduces wear on materials, and guarantees a long service life.

The extinguishing agent: ABC dry powder

When seconds count, ABC dry powder offers a decisive advantage. It combines rapid extinguishing action with maximum user safety. The cloud of extinguishing powder spreads over a wide area, providing protection against smoke and radiant heat.

  • High extinguishing power: ABC dry powder achieves greater effectiveness than other extinguishing agents on standardized test fires.
  • Reliable protection against re-ignition: An effective barrier layer prevents the supply of oxygen.
  • Versatile & safe: Ideal for fire classes A, B, and C, as well as for electrical systems (in accordance with VDE 0132).
  • Recyclable: ABC dry powder can be processed into fertilizer.

Fire-Extinguishing power for commerce and industry

With a rating of 43A / 233B and 12 extinguishing agent units (LE), the Gi6CS-03 ranks among the most powerful 6 kg powder fire extinguishers in its class. It is particularly well-suited for businesses where various fire risks ranging from wood and paper to fuels and electrical installations must be addressed at a single location.

For maximum extinguishing performance in a compact format, the Gi6CS-04 is the most economical solution. Its rating of 55A / 233B represents the highest achievable rating. For requirements involving a larger volume of extinguishing agent or for covering larger areas, we recommend the Gi9CS or Gi12CS models.

Versions

Capacity: 6 kg ABC-dry powder
Rating: 43A / 233B / C
Dimensions H x W x D ca. mm: 565 x 240 x 160
Weight ca. kg: 10,2
Throw range ca. m: 7
Discharge time ca. Sek.: 22
Operating temp. °C: -30 to +60

Packaging: Single packaging, 56 Units per palett

Capacity: 6 kg High performance ABC-dry powder
Rating: 55A / 233B / C
Dimensions H x W x D ca. mm: 565 x 240 x 160
Weight ca. kg: 10,2
Throw range ca. m: 7
Discharge time ca. Sek.: 22
Operating temp. °C: -30 to +60

Packaging: Single packaging, 56 Units per palett

Capacity: 9 kg ABC-dry powder
Rating: 55A / 233B / C
Dimensions H x W x D ca. mm: 605 x 275 x 195
Weight ca. kg: 15,1
Throw range ca. m: 8
Discharge time ca. Sek.: 23
Operating temp. °C: -30 to +60

Packaging: Single packaging, 30 Units per palett

Capacity: 12 kg ABC-dry powder
Rating: 55A / 233B / C
Dimensions H x W x D ca. mm: 730 x 310 x 195
Weight ca. kg: 19,0
Throw range ca. m: 8
Discharge time ca. Sek.: 24
Operating temp. °C: -30 to +60

Packaging: Single packaging, 30 Units per palett

Features

GPSR Information

DÖKA Feuerlöschgerätebau GmbH
Antonius-Raab-Straße 18
34123 Kassel
Deutschland

Kontakt

Product data sheet: see Downloads
Operating instructions and declaration of conformity: see Downloads
Material safety data sheet for extinguishing agents: see Downloads

Safety instructions

  • Operate the fire extinguisher in accordance with the pictograms and instructions printed on the fire extinguisher‘s operating plate, taking into account the additional information and instructions.
  • The minimum and maximum temperature limits specified on the operating plate must be observed. Do not expose to cold or heat radiation if this causes the minimum or maximum temperature limit to be exceeded or fallen short of. Store fire extinguishers in frost-free areas. Protect from UV radiation.
  • The use of CO2 and powder fire extinguishers can lead to electrostatic charging.
  • CO2 fire extinguishers may only be used when people are present in rooms if there is a free floor area of >5.5 m² per kg of CO2. There is a risk of suffocation. • Do not direct the extinguishing agent jet at people from a short distance, especially not at the head. There is a risk of suffocation and CO2 fire extinguishers can cause cold burns.
  • Fire extinguishers can be pressurised. Do not expose to force, do not open by force.
  • If pressurised parts are damaged or corroded, the fire extinguisher must be depressurised and repaired immediately by a competent person.
  • Only use fire extinguishers for their intended purpose. Do not make any structural modifications. • Fire extinguishers must be installed or set up in such a way that they are easily visible and accessible and protected against falling over or falling down and damage.
  • Never carry fire extinguishers loose in the vehicle. Transport is only permitted with proper securing and in the original sealed carton or equivalent safety measures. Special brackets are required to carry fire extinguishers on or in vehicles at all times, and these must be fitted professionally. Fire extinguishers must be mounted in such a way that they cannot be damaged by the expected vibrations or movements, or even fall out of the holder. If the fire extinguisher is to be mounted on the outside of the vehicle, it must also be placed in a protective container.
  • Keep fire extinguishers clean, do not use aggressive cleaning agents, only clean with a damp cloth.
  • Only have fire extinguishers completely emptied and depressurised disposed of by a recognised disposal company.
  • For cooking oil and cooking fat fires, only use fire extinguishers specially designed for fire class F!
  • Keep away from children

Packaging consisting of*:

Outer carton, cardboard, PAP 20
PE-LD protective film

* Details for standard shipping

  • Fire extinguisher
  • Wall bracket
  • Operating Instructions / Declaration of Conformity
Reference 1414-0100 Category Powder extinguishers

Technische Daten

Operating system Cartridge operated CS-Series
Fire class B Rating 233
Fire class C Yes
Capacity 12 kg 6 kg 9 kg
Extinguishing agent ABC-dry powder
Temperature range °C -30 to +60

Question about this product

 
Loading...
Back to top